Skip to content

Add SNMP sub-driver for Voltronics/Powershield UPS (PEN 43943) #3478

@hdcoffeeboy

Description

@hdcoffeeboy

It appears that neither Voltronic (ODM) nor PowerShield (Australian brand) have submitted their MIB file for NUT. I've approached PowerShield about it, but they've gone quiet on the subject. It appears that Voltronic is a fairly significant ODM, so if its possible to get their unbranded or self-branded sub-driver added, it would cover PowerShield, Orvaldi, Voltacon, Energico and other brands globally.

NUT (using the Home Assistant add-on in this instance) is providing detailed telemetry using the default SNMP driver, but no configuration or control.

Attached are the MIB files supplied by PowerShield. PowerShield also supplied the following information:

  1. Analog value
    Input voltage:1.3.6.1.4.1.43943.1.1.4.5.1.3.0
    Output voltage:1.3.6.1.4.1.43943.1.1.5.7.1.2.0 Frequency:1.3.6.1.4.1.43943.1.1.5.2.0
    Battery total voltage:1.3.6.1.4.1.43943.1.1.3.5.0
    Temp:1.3.6.1.4.1.43943.1.1.3.13.0
    Note: Above parameters value would be x10 of real value.
    Battery capacity:1.3.6.1.4.1.43943.1.1.3.4.0
    Output load:1.3.6.1.4.1.43943.1.1.5.7.1.7.0

  2. Alarm status

Ups model: 1.3.6.1.4.1.43943.1.1.5.1.0: 3: Line Mode
4: bypass mode
5: battery mode
8: battery test mode
Ups manufacturer: 1.3.6.1.4.1.43943.1.1.1.1.0
Ups version:1.3.6.1.4.1.43943.1.1.1.6.0
Test alarm:1.3.6.1.4.1.43943.1.1.5.1.0 Testing:8, Untest: other
Battery status: 1.3.6.1.4.1.43943.1.1.3.1.0 Battery low voltage: 3, battery normal: 2
Running status:1.3.6.1.4.1.43943.1.1.5.1.0 Line Mode: 3, bypass mode: 6
AC status:1.3.6.1.4.1.43943.1.1.3.1.0 AC break: 4, AC normal: 2

UPS_20250508.MIB.txt
RFC1628.mib.txt
UPSmib.mib.txt

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type
    No fields configured for issues without a type.

    Projects

    No projects

    Milestone

    No milestone

    Relationships

    None yet

    Development

    No branches or pull requests

    Issue actions